Home > Blog > Content

How to install and adjust the boom and nozzle on the boom sprayer?

Oct 14, 2024

The following points should be mastered when installing automatic sprinkler heads:
1. The arrangement of upright and drooping nozzles, including the spacing of nozzles on the same water distribution branch pipe and the spacing of adjacent water distribution branch pipes, should be determined according to the system's water spray intensity, nozzle flow coefficient and working pressure, and should not be less than 2.4m.
2. Except for ceiling-mounted nozzles and nozzles installed under the ceiling, the distance between the splash plate and the top plate of upright and drooping standard nozzles should not be less than 75mm and should not be greater than 150mm.
3. When the nozzle is arranged on a plane below the bottom of a beam or other obstacle, the distance between the splash plate and the top plate should not be greater than 300mm, and the vertical distance between the splash plate and the bottom of obstacles such as beams should not be less than 25mm and should not be greater than 1OOmm.
4. In places with a clearance height of no more than 8m, cross beams arranged with a spacing of no more than 4×4(m) can be arranged with one nozzle between the beams.
5. The distance between the splash plate of the horizontal side wall sprinkler and the top plate should not be less than 150mm and should not be greater than 300mm.

Send Inquiry